SimpliPHI ESS 6kW Inverter |
Overview |
Model Designation |
PHI-HB-INV-6kW |
Environmental Protection |
IP65 |
Protective Class |
I |
Battery Input Data |
Nominal Battery Voltage |
48VDC |
DC Voltage Range |
40 colspan='1' 62VDC |
Maximum Charging Voltage |
62VDC (Configurable) |
Maximum Charging Current |
100 A |
Maximum Discharging Current |
150 A |
Charging Curve |
3 Stages / Float |
Charging Strategy for Li-Ion Battery |
Self-adaption to BMS |
Number of DC Connections |
1 |
PV String Input Data |
Maximum DC Input Power |
7,500 W |
Nominal DC Voltage |
360VDC |
Maximum DC Input Voltage |
600VDC |
MPPT Range |
120 colspan='1' 550VDC |
Start-up Voltage / Initial Feed In Voltage |
125VDC / 160VDC |
Maximum Input Current per MPPT |
15 A |
Maximum Isc PV |
21 A |
Maximum Inverter Back Feed Current to Array |
0 A |
Number of MPP Trackers |
2 with 2 inputs each |
AC Output Data (On-grid) |
Nominal Apparent Power Output to Utility Grid |
6,000 VA |
Nominal Output Voltage |
220VAC / 240VAC L1-L2, 110VAC / 120VAC L-N |
Nominal Output Frequency |
50 / 60 Hz |
Output Frequency Range |
47.5 colspan='1' 51.5 Hz or 59.3 colspan='1' 60.5 Hz |
Output Voltage Range |
105.5- 132VAC per phase |
Inrush Current/Duration |
30 A per phase / 20 ms |
O/P DC Component |
<100 mA |
Output Power Factor |
>0.99 (Adjustable from 0.9 leading to 0.9 lagging) |
Output THDi (@Nominal Output) |
<3% |
Switch Over Time (Grid Down) |
<8 ms |
AC Output Data (Back-up) |
Maximum Output Apparent Power |
6,000VA |
Instantaneous Power (100ms) |
12,000VA |
Surge Power (5 sec) |
9,000VA |
Maximum Output Active Power |
6,000 W |
Nominal Output Voltage |
220VAC / 240VAC L1-L2, 110VAC / 120VAC L-N |
Nominal Output Frequency - Auto Sensing |
50/60 ( 0.1 Hz) |
Output THDv (@Linear Load) |
<3% |
Output THDv (@PF 0.8 Non-Linear Load) |
<5% |
Parallel Function |
Yes |
Parallel Units |
9 |
Automated Generator Start |
Included |
Efficiency |
Maximum Solar to Utility Efficiency |
96.50% |
Maximum Battery to Load Efficiency |
91.00% |
Protection |
Anti-Islanding Protection |
Integrated |
PV String Input Reverse Polarity Protection |
Integrated |
AFCI (Arc-Fault) |
Integrated |
Ground Fault Monitoring |
Integrated |
Insulation Resistor Detection |
Integrated |
Residual Current Monitoring Unit |
Integrated |
Output Over Current Protection |
Integrated - 90 A per phase |
Output Short Protection |
Integrated |
Rapid Shut Down Relay |
Integrated |
General Data |
Operating Temperature Range |
-13 - 140 F (-25 - 60 C) |
Transformerless |
Yes |
Consumption Modes |
UPS, Self-Consumption, TOU, Off- Grid Backup, Grid-Tied without Batteries |
Relative Humidity |
0 colspan='1' 90% |
Operating Altitude |
<13,123 ft (4,000 m) |
Cooling |
External Force Convection |
Noise |
<50 dB |
Dimensions (W x H x D) |
20.28 x 27.55 x 8.5 in (515 x 700 x 215.5 mm) |
Noise |
<50 dB |
Dimensions (W x H x D) |
20.28 x 27.55 x 8.5 in (515 x 700 x 215.5 mm) |
Communications Interface |
User Interface |
LCD / Phone Application (iOS & Android) |
Communication with BMS |
CANBUS |
Communications Between Inverters |
CANBUS |
Communication with Cloud - API with Grid Services |
via EnergyTrakTM Gateway |
Communication Port |
RS-232 |
Intelligent Slot |
RS232 / USB, BMS, Wi-Fi |
Certifications / Standards |
Grid Regulation |
UL 1741SA / SB-2020, IEEE1547.1-2020 |
Safety Regulation |
6-1, 6-4 IEC / EN 62109-1&2 |
EMC |
EN 61000-6-2, EN 61000-6-3 |